Modbus
Address
40033
40034
to
40100
Chapter 4 — Programming Considerations
Name
MBP Status
Not Defined
at this time
Values
0
to
3
Description
This register is used to
communicate the last Invalid
MBP Status value. Possible
values are as follows:
0 No error since power
cycle
1 Invalid Global Cmd
Request Most likely the
slave address for the
MBP is > 16 and is
configured for Global
Cmd
2 Invalid Global Length
The host is not configured
to send enough Global
Data to support this
node’s Modbus Plus
address
3 Invalid Write Range
An MSTR Type 1 write
cmd was received
attemtpting to write into
the 40011 to 40100
address range. The cmd
was disregarded by the
MBP with a successful
response returned to the
host.
Note that this register is only
cleared on power up, and will
only be updated when a new
error condition arises. Therefore
be aware that a non-zero value
will stay in the register after an
initial error condition until the
next power cycle.
Reserved for future use